NATIONAL STANDARD
TCVN 3890:2023
FIRE PROTECTION - FIRE PROTECTION EQUIPMENTS FOR BUILDING AND CONSTRUCTION - EQUIPMENT, INSTALLATION
Foreword
TCVN 3890:2023 supersedes TCVN 3890:2009.
TCVN 3890:2023 is developed by the Central Department of Fire safety, Firefighting, and Rescue, requested by the Ministry of Public Security, appraised by the Directorate for Standards, Metrology and Quality and issued by the Ministry of Science and Technology.
FIRE PROTECTION - FIRE PROTECTION EQUIPMENTS FOR BUILDING AND CONSTRUCTION - EQUIPMENT, INSTALLATION
1 Scope
1.1 This standard provides for installation and equipment of fire protection equipment, fire protection systems for buildings, constructions, urban areas, economic zones, industrial parks, industrial clusters, export-processing zones, hi-tech zones and other dedicated areas as prescribed [5], when:
- The construction is carried out;
- The renovation aims to increase scale or repurpose rooms, buildings and constructions;
- The renovation aims to increase scale of economic zones, industrial parks, industrial clusters, export-processing zones, hi-tech zones and other dedicated areas according to regulations [5].
- Fire and explosion hazard classes of rooms, buildings and construction are changed in a manner that increases the fire hazard.
1.2 In addition to complying with this standard, buildings and constructions shall comply with the technical regulation or standard specific to each type of building/construction. In the case of any discrepancy between this standards and other regulations, the more stringent regulations shall prevail.
1.3 For buildings and constructions on which specific regulations are unavailable, foreign or international fire safety standards may be applied in accordance with prevailing regulations or guidelines of the ministerial fire authority.
2 Normative references
The following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies.
TCVN 4530 Filling station - Specifications for design.
TCVN 4878 Fire protection - Classification of fires.
TCVN 4879 Fire protection - Safety signs.
TCVN 5307 Petroleum and petroleum products terminal - Design requirements.
TCVN 5738 Fire protection - Automatic fire alarm system - Technical requirements.
TCVN 5684 Fire safety for petroleum and petroleum products facilities - General requirements.
TCVN 5760 Fire extinguishing system - General requirements for design, installation and use.
TCVN 6100 Fire protection - Fire extinguishing media - Carbon dioxide.
TCVN 6101 Fire protection equipment - Carbon Dioxide extinguishing systems for use on premises Design and Installation.
TCVN 6223 Liquefied petroleum gas (LPG) store - Safety general requirements.
TCVN 6305 (all parts) Fire protection - Automatic sprinkler systems.
TCVN 7026 Fire fighting - Portable fire extinguishers - Performance and construction.
TCVN 7027 Fire fighting - wheeled fire extinguishers - Performance and construction.
TCVN 7161 (all parts) Gaseous fire - extinguishing systems - Physical properties and system design.
TCVN 7336 Fire protection - Water, foam automatic fire-extinguishing systems - Design and installation requirements.
TCVN 7435 (all parts) Fire protection - Portable and wheeled fire extinguishers.
TCVN 7568 (all parts) Fire detection and alarm systems.
TCVN 9255 Performance standards in building - Definition and calculation of area and space indicators.
TCVN 12110 Fire protection - Portable fire centrifugal pump with internal combustion engine - Technical requirements and test methods.
TCVN 12314 (all parts) Automatic activated fire extinguisher.
TCVN 13316 (all parts) Fire protection - Fire fighting vehicles.
TCVN 13332 Respiratory protective devices - Full face masks - Technical requirements and test methods.
TCVN 13333 Aerosol Fire-Extinguishing Systems - Specifications for design, installation, inspection and maintenance.
TCVN 13456 Fire protection - Emergency lighting and Exit sign - Design, installation requirements.
3 Terms and definitions
The terms and definitions in TCVN 4530, TCVN 4879, TCVN 5307, TCVN 5684, TCVN 5738, TCVN 6100, 6101, TCVN 6223, TCVN 6305 (all parts), TCVN 7026, TCVN 7027, TCVN 7161 (all parts), TCVN 7336, TCVN 7435 (all parts), TCVN 7568-1, TCVN 12110, TCVN 12314-1, TCVN 13316 (all parts), TCVN 13332, TCVN 13333 and TCVN 13456, and the following terms and definitions apply:
3.1
“Fire protection equipments” mean
Those include motor vehicles, equipment, machinery, tools, chemicals and support instruments used for fire protection and human and property rescue.
3.2
“Automatic fire extinguishing system” means
A fire extinguishing system that is automatically activated to discharge its extinguishant when the controlled factor(s) of the fire exceed the established threshold values in the protected zone and has the functions of monitoring the discharge and stopping/stopping activation of the discharge of its extinguishant.
NOTES:
- Monitoring signals must be transmitted to the fire alarm control panel;
- The function of discharge/activation stopping must be triggered manually.
3.3
“Hose reel” consists of
Specialized equipment including a turn off valve, a hose guide, and nozzle is installed and ready to deploy to deliver water to the fire.
3.4
“Outdoor fire fighting water supply system” means
A system of specialized equipment installed outside a building to supply water for firefighting purposes.
3.5
“Local fire alarms device” means
A device that automatically detects fire and issues an alarm using audible signals.
NOTE: Local fire alarms devices, when installed in the same building and construction, must be connected, ensuring that all fire alarms are emitted when one device is activated.
3.6
“Initial fire fighting facilities” consist of
Sand barrels and drums; shovels; blankets.
3.7
“Filter masks” mean
Personal protective equipment which is intended for protecting the user's respiratory system against smoke and noxious gases for a period of time and at certain concentrations of oxygen in the air.
3.8
“Self-contained Breathing Apparatus” means
Personal protective equipment consisting of a full-face mask and a respirator used to protect the user's respiratory system against airborne contaminants.
3.9
“Construction” means
A product created by human labor and with building materials and equipment installed therein, affixed to land, which possibly includes underground and surface components, underwater and water surface components and constructed according to design.
3.10
“Building” means
A structure whose primary function is to shelter, protect people or objects therein and which is partially or entirely covered and built on a fixed location.
3.11
“Multi-function building” means
A building that has multiple functions (e.g., a building can be designed for use as an office, for rendering commercial services, serving public activities, and may contain accommodations)
NOTE: A multi-function building must comply with regulations on equipment and installation of fire protection equipment applicable to multi-function buildings if the floor area dedicated to each occupancy of the building does not exceed 70% of the total floor area of said building (not including floor area used for technical system, fire protection, fire emergency holding areas, and parking).
3.12
“Production building” means
A building where production activities are conducted and humans are enabled to work and operate equipment.
3.13
“Cold storage” means
One or more rooms which are insulated and cooled to keep food and goods at a specified temperature.
3.14
A space contained within a building that serves a definite purpose and is limited by structures.
3.15
“Height for fire prevention and fighting”
The height specified in this standard means the height for fire prevention and fighting of a building (excluding the topmost technical floor) and is:
- The maximum distance from fire lane to the lowest point of the opening (window) on the exterior wall of the highest storey:
- Half of total distance from fire lane to the floor and to the ceiling of the topmost storey - if no openings (windows) are located on the exterior wall.
NOTE 1: If roof is utilized, the height for fire prevention and fighting of the building is the greatest distance from fire lane to the highest point of the wall surrounding the roof.
NOTE 2: When determining the height for fire prevention and fighting, the roof shall not be counted if it is not regularly occupied by humans.
NOTE 3: If balcony (loggia) or enclosing structures (guardrail) are available, height for fire prevention and fighting is the greatest distance from fire lane to the highest point of the guarding structures (guardrail).
3.16
“Occupied roof” means
A roof which is regularly occupied by humans (at least 2 consecutive hours or at least 6 hours within a period of 24 hours).
3.17
“Technical floor” means
A storey or a part thereof where technical rooms or technical equipment of the building is located. A technical floor can be a basement, a semi-basement, an attic, the topmost storey, or any storey in-between.
3.18
“Attic" means
A storey located in the space directly beneath the pitched roof where a part or the entire vertical surface of the storey is created by roof pitches or gables while the height (from the floor) of the surrounding walls (if any) must not exceed 1.5 m.
3.19
“Number of floors” means
The number of above-ground floors (including technical floors, roof access) and semi-basements, excluding the attic.
NOTES:
Roof access does not contribute towards the number of floor of a construction when its sole use is to shelter stairwell/elevator shaft and cover technical equipment (if any) of the construction and when roof access area does not exceed 30% of roof area.
With respect to a single-family home, a mezzanine shall not be counted as a storey of that house if the floor area of such mezzanine does not exceed 65% of the floor area of the storey underneath.
With respect to an industrial building, the floor of each supporting platform and mezzanine that is located at any elevation and does not exceed 40% of a storey’s area shall not contribute towards the number of storeys of such industrial building.
With respect to houses, home-type structures or buildings with multiple stories built on floor levels (exclusive of single-family homes and industrial buildings), mezzanines are not counted as stories thereof only when they are designed for use as technical spaces (e.g. technical floor levels at the beds of swimming pools, floor levels where generators are placed or other equipment) and their floor area does not exceed 10% of the floor area of the storey underneath and does not exceed 300 m2. In a construction, only one mezzanine, which is not counted as a storey of the construction, is allowed.
3.20
“Volume”
The volume specified in this standard means the volume of an independent house, construction/construction item. It is calculated according to TCVN 9255.
3.21
"Area”
The area specified in this standard means the total floor area of a house, construction/construction item independent of its structure. It is calculated according to TCVN 9255.
NOTE: If the buildings have maintained the safety distance for fire prevention and fighting, escape and fire spread prevention and is connected by passage-way (bridge), the calculation of the separate area and volume of each building is permitted.
4 General provisions
4.1 Buildings, constructions and fire compartments shall, according to the nature of functional fire hazard, be classified into F1, F2, F3, F4 and F5 classes; buildings, constructions and rooms with manufacturing and storage occupancies shall, according to fire and explosion hazards, be classified into A, B, C, D and E classes as prescribed [17].
4.2 Buildings, constructions, items/zones, rooms, chambers and equipment (hereinafter referred to as “buildings and constructions”), urban areas, economic zones, industrial parks, industrial clusters, export-processing zones, hi-tech zones and other dedicated areas as prescribed [5] shall, regardless of their owner and managing unit of a legal entity, be provided with fire protection equipment and systems in accordance with the regulations set out in this standard.
4.3 Types of fire fighting equipment, fire fighting methods and types of extinguishants must be selected in a manner that is relevant to the nature and degree of fire hazards in buildings and constructions, to each type of fire and to capacity and efficiency of fire fire-fighting facilities and each type of extinguishant specified in 4.4 and related applicable technical standards.
4.4 The fire-fighting efficiency of extinguishants is provided in Table 1.
Table 1 - Fire-fighting efficiency of extinguishants
Extinguishant |
Fire-fighting efficiency by fire class |
|||||||
A |
B |
C |
D |
|||||
A1 |
A2 |
B1 |
B2 |
D1 |
D2 D3 |
|||
Water |
++ |
- |
- |
- |
||||
Foam, water-based extinguishant |
Water-based extinguishant |
++ |
+ |
- |
- |
|||
High expansion foam concentrate |
+ |
- |
++ |
+ |
- |
- |
||
Low and medium expansion foam concentrate |
+ |
+ |
++ |
+ |
- |
- |
||
Gas |
CO2 |
- |
+ |
+ |
- |
|||
Nitrogen, HFC-227ea, Inergen, Argon, FK 5-1-12, etc. |
+ |
+ |
+ |
- |
||||
Powder |
BC powder |
- |
++ |
++ |
- |
|||
ABC powder |
+ |
- |
||||||
ABCD powder |
++ |
- |
||||||
Aerosol |
+ |
+ |
+ |
- |
||||
NOTE: Fire is classified according to TCVN 4878 and TCVN 5760. “++” means Very effective. “+” means appropriate for fire extinguishing. “-” means inappropriate for fire extinguishing. BC powder is used to extinguish class B and C fires. ABC powder is used to extinguish class A, B and C fires. ABCD powder is used to extinguish class A, B, C and D fires. |
- Gaseous extinguishants are only used in areas where the extinguishing concentration is maintained for the specified hold time in accordance with TCVN 7161-1, TCVN 6101 and TCVN 13333. CO2 extinguishant is only used in normally unoccupied areas.
4.5 When the renovation is carried for the purpose of scale increase or repurposing or the fire hazard and explosion class of the rooms, buildings and constructions are changed in a manner that increases the fire hazard of such rooms, buildings and constructions, this standard shall be applied accordingly.
4.6 The whole building should be equipment with an automatic fire extinguishing system if the total area of the building’s rooms subject to automatic fire extinguishing system equipment is 40% or more of the total floor area of that building.
4.7 If the building’s rooms belonging to functional fire hazard class F5 (excluding F5 rooms in the building belonging to other functional fire hazard category, the automatic fire extinguishing system have been equipped with an automatic fire extinguishing system inter-connected with the fire alarm control panel, automatic fire detectors are not required to be installed (other equipment of the automatic fire alarm system must be installed according to regulations).
4.8 Buildings and constructions must be equipped with fire protection equipment and systems by relying on the analysis of their functions, nature of fire hazards and other factors related to the protection of people and property. Buildings and constructions other than those specified in Annexes A, B, C, D, E, F and G are required to be equipped with fire protection equipment and systems which are the same as those intended for buildings and constructions of similar purposes.
4.9 Automatic fire alarm systems or devices intended for buildings must be connected to the fire database management system and incident reporting system of the fire police authority according to regulations [9], [10].
4.10 When determining the equipment of an automatic fire extinguishing system and/or automatic fire alarm system, select an appropriate system for the entire building first (Table A.1), then for each item/area (Table A.2) and rooms in the building (Table A.3) as well as equipment located within a construction (Table A.4).
4.11 The buildings not divided or divided into rooms by frame structures: walls and floors with a fire-resistance rating less than REI 45, partitions with a fire-resistance rating less than REI 45 shall be equipped with an automatic fire alarm system and/or automatic fire extinguishing system corresponding to the room according to Table A.3.
4.12 In the buildings and constructions specified in Annex A must be equipped with an automatic fire extinguishing system and/or automatic fire alarm system, apart from the premises:
- Production areas involving wet processes, swimming pools, showers, wash rooms, toilets;
- Rooms of class D of fire hazard;
- Single-loaded corridors;
- Stairwells;
- Pressurizes fire protection vestibules;
- Areas in which there are no fire hazards.
4.13 Apartments of buildings belonging to F1.3 category with a height of no more than 75 m are only required to be equipped with sprinklers of the water automatic fire extinguishing system at the door of the apartments (installed inside the apartment).
4.14 Fire protection equipment and systems specified in this standard must be inspected and maintained on a periodic basis in compliance with regulations of law and related applicable technical regulations or instructions of the manufacturer.
4.15 In some specific cases, several requirements of this standard applicable to specific constructions may be replaced when there is a technical justification for complementary and alternative solutions and grounds of those solutions to ensure fire safety of the constructions. This justification must be approved by the ministerial fire authority.
5 Regulations on Equipment and installation of fire protection equipment and systems.
5.1 Equipment and installation of fire extinguishers.
5.1.1 Equipment and installation of portable and wheeled fire extinguishers.
5.1.1.1 All areas in buildings and constructions, including areas equipped with fire extinguishing systems, must be equipped with portable or wheeled fire extinguishers.
5.1.1.2 The selection, equipment and installation of fire extinguishers shall comply with the regulations laid down in Articles 6 and 7 of TCVN 7435-1.
5.1.1.3 For narrow and long areas or areas with different and adjacent floor levels, a fire extinguisher must be installed so that the travel distance from the position of a fire extinguisher to the farthest point to be protected does not exceed that specified in 5.1.1.2.
5.1.1.4 On the same floor or storey, if the premises is separated into different areas by walls, partitions or other obstacles without any passage-way, fire extinguishers must be installed separately in accordance with 5.1.1.2 and 5.1.1.3.
5.1.1.5 The number of fire extinguishers reserved must not be less than 10% of the total number of fire extinguishers intended for replacement where necessary (no more than 100 of each type).
5.1.1.6 Fire extinguishers must be placed in conspicuous and easily accessible locations and should be red. If it is difficult to identify them, signs that show their locations may be used and the regulations set out Article 5 of TCVN 7435-1 shall be complied with. Fire extinguishers must not be placed in a single location, except for the case where they are placed in a storage area in accordance with 5.1.1.5.
Fire extinguishers should be always available for immediate use and located:
a) where they will be readily seen by any person following an escape route;
b) most suitably, near to room exits, stairways, corridors, and passage-ways;
c) in similar positions on each floor, where floors are of similar appearance.
Fire extinguishers should not be located:
a) where a potential fire might prevent access to them;
b) close to heating appliances that might affect quality and efficiency of the extinguishers;
c) in concealed positions behind doors, in cupboards or deep recesses;
d) where they might cause obstruction to exit routes;
e) in positions in rooms or corridors away from exit routes unless they are necessary to cover a particular hazard;
f) where they might be damaged by daily activities.
5.1.1.7 Portable and wheeled fire extinguishers must have the functions and meet the specifications specified in TCVN 7026 and TCVN 7027.
5.1.2 Equipment and installation of hanging type automatic diffusion dry-powder fire extinguishers
5.1.2.1 Hanging type automatic diffusion dry-powder fire extinguishers must conform to TCVN 12314-1.
5.1.2.2 Based on the actual conditions of buildings and constructions, they may be wall or ceiling mounted with an appropriate height to effectively cover the area to be protected as announced by the manufacturer. In any case, the distance from the temperature sensor to the ceiling should not exceed 40 cm.
5.1.2.3 Hanging type automatic diffusion dry-powder fire extinguishers may be installed in kitchen areas of restaurants, boiler rooms and laundry areas with an area not exceeding 100 m2. If installed in an area of more than 100 m2, it is recommended that such area be divided into the areas by a fire separating wall (with a fire-resistance rating at least REI 45) or a fire separating partition (with a fire-resistance rating at least EI 45), each of which must not exceed 100 m2.
5.1.3 Equipment and installation of automatic activated fire extinguishers - fire suppression cylinders
5.1.3.1 Automatic activated fire extinguishers - fire suppression cylinders must conform to TCVN 12314-2.
5.1.3.2 An automatic gas fire extinguishing system may be replaced with an automatic activated fire extinguisher - fire suppression cylinders (design it in such a way that the discharge monitoring function is added and discharge signals are transmitted to the fire alarm control panel) in normally unoccupied areas with an area not exceeding 100 m2. If installed in an area of more than 100 m2, it is recommended that such area be divided into the areas by a fire separating wall (with a fire-resistance rating at least REI 45) or a fire separating partition (with a fire-resistance rating at least EI 45), each of which must not exceed 100 m2.
5.2 Equipment and installation of automatic fire alarm systems and local fire alarms devices.
5.2.1 The list of buildings; items/areas; rooms and equipment to be protected by automatic fire alarm systems and local fire alarms devices is provided in Annex A.
5.2.2 The selection and equipment of local fire alarms devices shall be carried out as similar devices of an automatic fire alarm system.
5.2.3 Technical specifications for automatic fire alarm systems are specified in TCVN 5738 and TCVN 7568.
5.3 Equipment and installation of automatic fire extinguishing systems and equipment.
5.3.1 The list of buildings; items/areas; rooms and equipment subject to equipment and installation of automatic fire extinguishing systems and equipment is provided in Annex A.
NOTE: Automatic activated fire extinguishing equipment includes automatic diffusion fire extinguishers - hanging type dry powder fire extinguishers and automatic activated fire extinguishers - fire suppression cylinders.
5.3.2 Extinguishants used in automatic fire extinguishing systems must have fire-fighting efficiency suitable for any type of fire of area to be protected as prescribed in Article 4.3 and in accordance with the requirements for protection.
5.3.3 Upon installation of an automatic fire extinguishing system that discharges an extinguishant which is dangerous to humans, it is required to determine the escape time to ensure the last person to escape the room or area to be protected before the automatic system releases the extinguishant. Other regulations on selection and installation of automatic fire extinguishing systems are enshrined in TCVN 5760, TCVN 6101, TCVN 6305, TCVN 7161, TCVN 7336, TCVN 13333 and other related Vietnam standards issued by the supervisory Ministry.
5.4 Equipment and installation of indoor hose reel systems and outdoor fire fighting water supply systems.
5.4.1 Equipment and installation of indoor hose reel systems.
5.4.1.1 Buildings must be equipped with indoor hose reel systems specified in Annex B.
5.4.1.2 Indoor hose reel systems of production buildings, warehouses with high fire hazard, buildings with a height of 25 m or more, markets, shopping malls, supermarkets, hotels, discotheques, karaoke businesses, bars, night clubs, railway stations, seaport service buildings, inland port service buildings, theaters and cinemas must regularly have water which is maintained at a pressure that facilitate automatic activation of such systems.
5.4.1.3 The indoor hose reel system may be installed separately or in combination with the water automatic fire extinguishing system. The indoor hose reel system must have breeching inlets installed outside to take water from the fire engine pump or portable fire pump.
5.4.1.4 The indoor hose reel system shall not be equipped in buildings, areas and rooms that use or store substances which, in contact with water, may cause fire, explosion or widespread flame.
5.4.2 Equipment and installation of outdoor fire fighting water supply systems.
5.4.2.1 Outdoor fire fighting water supply systems shall be equipped according to the regulations set out in Annex C.
5.4.2.2 Where the fire hydrants can cover any point of a building or construction along its width and cover radius of each hydrant which does not exceed 200 m along the path of travel of the fire hoses outside the building, from the fire hydrant or water intake area of ponds, lakes, rivers or public water tanks, if:
- The flow rate and volume of fire fighting water are achieved according to regulations, the outdoor fire fighting water supply system is not required.
- The flow rate and volume of fire fighting water are not achieved according to regulations, the outdoor fire fighting water supply system is required (when calculating the flow rate of the outdoor fire fighting water supply system, it is permissible to combine different water sources).
5.4.2.3 The combination of the outdoor fire fighting water supply systems and the domestic and production water supply system is permitted.
5.5 Installation and equipment of fire-fighting vehicles.
5.5.1 Warehouses, airports, seaports, key economic, political and social - cultural establishments, industrial parks, export-processing zones, hi-tech zones and industrial clusters shall, in addition to the fire extinguishing system, be equipped with fire-fighting vehicles according to TCVN 13316 Fire protection - Fire fighting vehicles (all parts), national standards, international and foreign standards permitted for application in Vietnam. The minimum number of fire-fighting vehicles to be equipped is prescribed in Annex D.
5.5.2 Fire engines, fire boats and portable fire pumps for buildings and constructions must:
a) have specifications and performance relevant the type of buildings and constructions to be protected;
b) have extinguishants, attached instruments and equipment in accordance with regulations;
c) Portable fire pumps must meet the technical specifications specified in TCVN 12110.
5.6 Equipment and installation of rudimentary demolition facilities and tools; filter masks and self-contained breathing apparatus
5.6.1 Equipment and installation of rudimentary demolition facilities and tools.
5.6.1.1 Buildings and constructions must be equipped with rudimentary demolition facilities and tools specified in Annex E.
5.6.1.2 Rudimentary demolition facilities and tools for buildings and constructions must be located in the area dedicated for storing fire-fighting equipment.
5.6.2 Equipment and installation of filter masks and self-contained breathing apparatus.
5.6.2.1 Buildings and constructions must be equipped with filter masks and self-contained breathing apparatus specified in Annex F. It is recommended that other buildings and constructions such as apartment buildings, hospitals, offices, theatres, cinemas, etc. be equipped with filter masks.
5.6.2.2 Filter masks for buildings and constructions must be located in equipment cabinets in the escape corridor on each floor; self-contained breathing apparatus must be located in the fire command center in a conspicuous and easily accessible position following the manufacturer's instructions.
5.6.2.3 Filter masks must have filters in accordance with applicable standards and technical regulations [19]. Self-contained breathing apparatus must have a full face mask that meets the requirements specified in TCVN 13332.
5.7 Equipment and installation of emergency and exit lighting equipment; public address and evacuation instruction systems.
5.7.1 Equipment and installation of emergency and exit lighting equipment.
5.7.1.1 Equipment and installation of emergency and exit lighting equipment shall be equipped in all buildings and constructions (except for single-family homes)
5.7.1.2 The selection and installation of emergency and exit lighting equipment are specified in TCVN 13456.
5.7.2 Equipment and installation of public address and evacuation instruction systems
5.7.2.1 Buildings and constructions must be equipped with public address and evacuation instruction systems specified in Annex G.
5.7.2.2 Public address and evacuation instruction systems shall be such that all occupants in buildings and constructions could clearly hear the alarm and instructions in case of emergency.
5.7.2.3 Audible signals of public address and evacuation instruction systems must have a total sound level (sound level of the continuous noise together with the sound from the warning signals generated) of at least 75 dBA at 3 m distance from the alarm signal, but no more than 120 dBA in any position.
5.7.2.4 The audible signals of public address and evacuation instruction systems must produce a sound level at least 15 dBA above the sound level of the continuous noise in a room. The sound level shall be measured at a height of 1.5 m from the floor.
5.7.2.5 In a sleeping room, audible signals of public address and evacuation instruction systems shall produce a sound level at least 15 dBA above the sound level of the continuous noise in the room but the total sound level must be at least 70 dBA and no more than 120 dBA. The sound level shall be measured at the head pillow level.
5.7.2.6 Wall-mounted fire alert loudspeakers and evacuation alert control equipment must be arranged such that their upper part is at least 2.3 m from the floor and at least 0.15 m from the ceiling.
5.7.2.7 In areas where people are protected by noise cancellation devices and rooms where the noise exceeds 95 dBA, the public address and evacuation instruction systems must include light alarm. The use of flashing alarm equipment is permitted.
5.7.2.8 Voice alert loudspeakers and evacuation equipment must produce a sound with a frequency in the range from 200 Hz to 5 000 Hz.
5.7.2.9 The number of voice alert loudspeakers and evacuation equipment, their installation and capacity shall be such that the sound level in all areas conforms to the regulations enshrined in this standard.
5.8 Installation and equipment of initial fire fighting facilities.
5.8.1 Initial fire fighting facilities for warehouses, shops and production facilities are specified in Annex H.
5.8.2 Initial fire fighting facilities for petroleum and petroleum products terminals, filling stations, petroleum storages, terminals and pipelines, and LPG stations are specified in TCVN 5307, TCVN 4530, TCVN 5684, TCVN 6223 and other related Vietnam standards issued by the supervisory Ministry.
5.8.3 For other facilities, the equipment of initial fire fighting facilities shall depend on the conditions and requirements of each facility.
5.8.4 Initial fire fighting facilities shall be located in each area which is fit for their intended use in a manner that they do not obstruct escape routes, passage-ways and other activities; are protected from sun, rain and environmental destruction. Each sand container shall come with at least 2 shovels. Fire-fighting sand containers shall be covered to prevent the entry of dirty objects.
5.8.5 Initial fire fighting facilities should be painted red.
Annex A
(normative)
Equipment of automatic fire alarm systems, local fire alarms devices and automatic fire extinguishing system
Table A.1 - For buildings
No. |
Type of building |
Automatic fire extinguishing system (1) |
Automatic fire alarm system |
1. |
Single-family homes |
With height of 25 m or more |
7 storeyed or more or 25 m or more high (equipment of local fire alarms devices is permitted) |
2. |
Single-family homes not more than 30% of the area of which is used for trading and/or production of highly flammable goods and substances (2) |
With height of 25 m or more |
3 storeyed or more or with volume of 1 500 m3 or more (equipment of local fire alarms devices is permitted if the house has fewer than 5 storeys and a volume of less than 2 500 m3) |
3. |
Multi-function buildings |
With height of 25 m or more or area of 5 000 m2 or more |
3 storeyed or more or with volume of 1 500 m3 or more (equipment of local fire alarms devices is permitted if the building has fewer than 5 storeys and a volume of less than 1 500 m3) |
4. |
Apartment buildings, tenements; dorm |
With height of 25 m or more or area of 10 000 m2 or more |
5 storeyed or more or with volume of 2 500 m3 or more (equipment of local fire alarms devices is permitted if the building has fewer than 5 storeys and a volume of less than 5 000 m3) |
5. |
Buildings for provision of accommodation services (inns); hotels, motels and accommodation establishments founded according to regulations [1] (except for camping sites) |
With height of 25 m or more or area of 5 000 m2 or more |
3 storeyed or more or with volume of 2 500 m3 or more (equipment of local fire alarms devices is permitted if the building has fewer than 5 storeys and a volume of less than 5 000 m3) |
6. |
Nursing homes, people with disabilities-care institutions |
Regardless of scale |
Regardless of scale (equipment of local fire alarms devices is permitted if the building has fewer than 3 storeys and a volume of less than 1 000 m3) |
7. |
Nurseries, kindergartens, preschools |
4 storeyed or more (excluding the topmost technical floor) |
With 100 children or more or with volume of 1 000 m3 or more (equipment of local fire alarms devices is permitted if the height is less than 15 m and the volume is less than 1 500 m3) |
8. |
Schools and educational institutions according to regulations [2] (except for section 6 of this table) |
With height of 25 m or more |
5 storeyed or more or with volume of 5 000 m3 or more (equipment of local fire alarms devices is permitted if the volume is less than 2 000 m3) |
9. |
Air traffic control towers, airport terminals, railway terminals, gondola lift waiting lounges, seaport, inland port and inland waterway ports service buildings, bus stations, rest stops |
With height of 25 m or more or area of 10 000 m2 or more |
Regardless of scale. (equipment of local fire alarms devices is permitted if the building has fewer than 3 storeys and the volume is less than 1 000 m3) |
10. |
Post offices, radio and television stations, telecommunications facilities: service facilities |
With height of 25 m or more or area of 5 000 m2 or more |
3 storeyed or more or with volume of 1 500 m3 or more |
11. |
Cultural centers, event centers |
With height of 25 m or more or area of 5 000 m2 or more |
3 storeyed or more or with volume of 1 500 m3 or more |
12. |
Book storage buildings; libraries |
With height of 25 m or more or area of 5 000 m2 or more |
Regardless of scale (equipment of local fire alarms devices is permitted if the volume is less than 1 500 m3) |
13. |
Food and beverage stores, beauty salons, massage service buildings; building blocks of amusement parks, aquariums |
With height of 25 m or more or area of 5 000 m2 or more |
With volume of 1 000 m3 or more (equipment of local fire alarms devices is permitted if the building has fewer than 3 storeys and volume of less than 1 500 m3) |
14. |
Sports stadiums, sports palaces |
With height of 25 m or more |
With volume of 1 500 m3 or more or 200 seats or more (equipment of local fire alarms devices is permitted if the volume is less than 5 000 m3) |
15. |
Buildings for medical examination and treatment and patient dormitories of hospitals, health stations, clinics, sanitariums, rehabilitation and orthopedic centers, centers for disease control and prevention, health centers, other health facilities according to applicable regulations [3] |
With height of 25 m or more or area of 2 000 m2 or more |
3 storeyed or more or with volume of 1 000 m3 or more |
16. |
Administrative buildings 3) |
With height of 25 m or more or area of 5 000 m2 or more |
5 storeyed or more or with a volume of 1 500 m3 or more (equipment of local fire alarms devices is permitted if the building has fewer than 5 storeys and volume of less than 5 000 m3) |
17. |
Electronics stores, department stores, convenience stores and stores for sale of highly flammable goods and substances 4) |
||
17.1. |
Situated in basement or semi-basement |
With area of 200 m2 or more |
Regardless of scale |
17.2. |
Situated on the ground |
With height of 25 m or more or area of 3 500 m2 or more |
3 storeyed or more or with a volume of 1 000 m3 or more (equipment of local fire alarms devices is permitted if the building has fewer than 5 storeys and volume of less than 1 500 m3) |
18. |
Commercial buildings 5) (except for car showrooms), theatres, cinemas, circuses |
||
18.1. |
Situated in basement or semibasement |
With area of 200 m2 or more |
Regardless of scale |
18.2. |
Situated on the ground |
||
18.2.1. |
One storeyed, two storeyed |
With area of 3 500 m2 or more |
Regardless of scale |
18.2.2. |
Three storeyed or more |
Regardless of scale |
Regardless of scale |
18.3. |
Buildings for sale of flammable and highly flammable liquids (except for goods contained in cans and bottles with a capacity of not more than 20 liters) |
Regardless of scale |
Regardless of scale |
19. |
Buildings in section 3, sections 10 to 18 of this table at fire resistance level IV-V |
With area of 1 200 m2 or more |
Regardless of scale (equipment of local fire alarms devices is permitted if the area is less than 300 m2) |
20. |
Karaoke, discotheque, bar and night club service buildings |
||
20.1. |
Situated in basement or semibasement |
Regardless of scale |
Regardless of scale |
20.2. |
Situated on the ground |
||
20.2.1. |
One or two storeyed |
With area of 500 m2 or more |
Regardless of area |
20.2.2. |
Three storeyed or more |
Regardless of area |
Regardless of area |
21. |
Religious buildings |
With height of 25 m or more |
4 storeyed or more |
22. |
Museums, exhibition buildings |
||
22.1. |
Situated in basement or semibasement |
With area of 200 m2 or more |
Regardless of scale |
22.2. |
Situated on the ground |
||
22.2.1. |
One storeyed, two storeyed |
With area of 1 000 m2 or more |
Regardless of scale |
22.2.2. |
Three storeyed or more |
Regardless of scale |
Regardless of scale |
23. |
Fire stations and brigades |
With height of 25 m or more |
5 storeyed or more or with volume of 5 000 m3 or more |
24. |
Car and moped garages and showrooms 6) |
||
24.1. |
Of enclosed type |
||
24.1.1. |
Situated in basement or semi-basement or on the ground, 02 storeyed or more |
Regardless of area |
Regardless of area |
24.1.2. |
A storey on the ground |
||
24.1.2.1. |
Fire resistance levels I, II and III of S0 grade structural fire hazard |
With area of 7 000 m2 or more |
Regardless of area |
24.1.2.2. |
Fire resistance levels I, II and III of S1 grade structural fire hazard |
With area of 3 600 m2 or more |
Regardless of area |
24.1.2.3. |
Fire resistance level IV of S0 grade structural fire hazard |
With area of 3 600 m2 or more |
Regardless of area |
24.1.2.4. |
Fire resistance level IV of S1 grade structural fire hazard |
With area of 2 000 m2 or more |
Regardless of area |
24.1.2.5. |
Fire resistance level IV of S2 and S3 grades structural fire hazard |
With area of 1 000 m2 or more |
Regardless of area |
24.1.3. |
Automated parking garages |
Regardless of scale |
- |
24.2. |
Of exposed type 7) |
||
24.2.1. |
Distance from any point to the excluded side: no more than 12 m |
- |
With area of 4 000 m2 or more or volume of 15 000 m3 or more or 3 storeyed or more |
24.2.2. |
Distance from any point to the excluded side: more than 12 m |
With area of 4 000 m2 or more or volume of 15 000 m3 or more or 3 storeyed or more |
Regardless of area |
25. |
Cattle and poultry farms 8) |
- |
With area of 10 000 m2 or more |
26. |
Buildings for processing and storage of granular agricultural products 8) |
With area of 1 000 m2 or more |
With area of 500 m2 or more |
27. |
Warehouses of fire hazard class C with goods on racks > 5.5 m high |
Regardless of scale |
Regardless of scale |
28. |
Warehouses of fire hazard class B and C with 2 storeys or more |
Regardless of scale |
Regardless of scale |
NOTES: 1) A building having 2 or more functions is not required to be equipped with an automatic fire extinguishing system as specified in Table A.1 but any functional part of the building whose scale is required to be equipped with an automatic fire extinguishing system according to Table A.1 must be equipped with an automatic fire extinguishing system. When karaoke, discotheque, bar or night club business is conducted in a building of other purpose but the part intended for karaoke, discotheque, bar or night club business of the building whose scale is required to be equipped with an automatic fire extinguishing system according to Table A.1 or intended for karaoke, discotheque, bar or night club business is situated on the third storey or more, the whole building must be equipped with an automatic fire extinguishing system. 2) Only an automatic fire alarm systems or local fire alarms device may be equipped in the business and production area, however, on each storey of the building, there must be an audio warning device that is connected with the automatic fire alarm system or local fire alarm device. 3) Administrative buildings include premises of regulatory authorities at all levels, office buildings of enterprises and socio - political organizations. 4) Stores for sale of highly flammable goods and substances include stores for sale of furniture, clothing, bedding, books, votive papers and stores of a similar nature. 5) Commercial buildings include markets, supermarkets and shopping malls. An automatic fire extinguishing system is not required to be installed in storage and processing areas for the sale of meat, fish, fruits and vegetables (in non-flammable packaging), pots and pans, non-flammable equipment, goods and materials. 6) Automatic fire extinguishing is not mandatory in underground single-storey garages built on open ground and capable of up to 25 parking spots; With respect to single-storey or 2 storey automobile garages separated into compartments (by class 1 fire separating partition) having exits leading directly outside from each compartment, automatic fire extinguishing and fire alarm systems are not required to be equipped provided that each compartment contain no more than 2 automobiles. Automatic fire extinguishing and fire alarm systems are not required to be equipped in buildings for moped storage and display which have no more than 02 storeys and an area of no more than 1 000 m2. 7) Exposed buildings mean those not covered externally by walls. A building is also considered to be exposed if two of its longest facing sides are excluded. A side is considered to be excluded if the total excluded area along it accounts for at least 50% of its external area on each level. 8) Automatic fire extinguishing and fire alarm systems are not required to be equipped in exposed buildings for cattle and poultry breeding and buildings for processing and storage of granular agricultural products. |
Table A.2 – For items/areas
No. |
Items/areas |
Automatic fire extinguishing system |
Automatic fire alarm system |
1. |
Cable structures 1) of power plants (exclusive of cables placed outside buildings and constructions) |
Regardless of scale |
Regardless of scale |
2. |
Cable structures 1) of electrical substations (exclusive of cables placed outside buildings and constructions) |
||
2.1. |
With voltage of 500 kV or higher |
Regardless of scale |
Regardless of scale |
2.2. |
With voltage of less than 500 kV. |
- |
Regardless of scale |
3. |
Cable structures 1) of electrical substations with voltage of 110-220kV (exclusive of cables placed outside buildings and constructions) having transformers with capacity: |
||
3.1. |
63 MVA or more |
Regardless of scale |
Regardless of scale |
3.2. |
Less than 63 MVA |
- |
Regardless of scale |
4. |
Cable cellars of production buildings and civil buildings where cables or conductors with voltage of 220 V or more is laid: |
||
4.1. |
Cellar volume more than 100 m3 |
12 strands or more |
5 strands or more |
4.2. |
Cellar volume from 10 m3 to 100 m3 |
- |
5 strands or more |
5. |
Closed conveyors transporting highly flammable materials |
With height of 25 m or more |
With height of 25 m or more |
6. |
The space above the false ceiling or under the raised floor of the areas 2) in rooms and buildings equipped with automatic fire extinguishing systems and/or automatic fire alarm systems 3) has: |
||
6.1. |
Technical pipelines covered with flammable materials Ch2-Ch4, regardless of mass |
Regardless of area and volume |
Regardless of area and volume |
6.2. |
Cable trays (cable bundles) with voltage of 220V or more and total volume of flammable substances Ch2-Ch4 is 0.007 m3/meter in length or more |
Regardless of area and volume |
Regardless of area and volume |
6.3. |
Cable trays (cable bundles) with voltage of 220V or more and total volume of flammable substances Ch2-Ch4 is 0.0015 m3/meter in length to less than 0.007 m3/meter in length |
- |
Regardless of area and volume |
NOTES: 1) Cable structures covered by this standard include cellars, tunnels, wells, raised floors, enclosed troughs and chambers for laying cables (including cooperation with other utilities). 2) Areas which satisfy the requirements set out in 6.1, 6.2 and 6.3 of this table include: - Escape corridors, halls, lobbies; - Rooms that have 50 persons or more; - Rooms of functional fire-hazard classes F1.1 and F4.1 and karaoke, discotheque, bar and night club services. Irrigators and fire detectors may be located in positions of technical pipelines and/or cable trays in the space above the suspended ceiling. 3) Cable structures located above the suspended ceiling and under the raised floor are not required to be equipped with automatic fire extinguishing and alarm systems (except for 1 to 3 of this table). To be specific: - Cables which are threaded onto conduits or sheathed with a non-flammable or flammable material Ch1; - Single cables (conductors) for powering lighting systems and communication cable systems. |
Table A.3- For rooms
No. |
Protected objects |
Automatic fire extinguishing system |
Automatic fire alarm system |
1. |
Storerooms |
||
1.1. |
Belonging to class A and B fire hazards |
With area of 300 m2 or more |
Regardless of area |
1.2. |
For rubber, resin beads; matches, alkali metals, pyrotechnic products; wool, fur; other flammable substances with small density (less than 3 kg/m3) |
Regardless of area |
Regardless of area |
1.3. |
Containing non-flammable goods but stored in flammable packaging (with fire load density 1 MJ/m2 to 180 MJ/m2) |
- |
With area of 300 m2 or more |
1.4. |
Belonging to class C fize hazard (excluding rooms mentioned in 1.2 and 1.3 of this table) when situated: |
||
1.4.1. |
In basement or semibasement |
Regardless of area |
Regardless of area |
1.4.2. |
On the ground |
With area of 300 m2 or more |
With area of 300 m2 or more |
1.5. |
Cold stores |
- |
With area of 300 m2 or more |
2. |
Production rooms |
||
2.1. |
Belonging to class A and B fire hazards |
With area of 300 m2 or more |
Regardless of area |
2.2. |
Belonging to class C fize hazard (excluding rooms located in buildings and facilities for processing and storage of granola agricultural products) when situated: |
||
2.2.1. |
In basement or semibasement |
Regardless of area |
Regardless of area |
2.2.2. |
On the ground |
With area of 1 000 m2 or more |
With area of 300 m2 or more |
2.3. |
Rooms for production of highly flammable liquids: solvents, paints, glues, mastics, impregnation compounds, synthetic rubber; rooms for production of aluminum powder suspension, rubber adhesives; rooms for paints, synthetic rubber, compressor rooms using gas turbines, petroleum and diesel heating rooms |
Regardless of area |
Regardless of area |
3. |
Communication rooms |
|
|
3.1. |
Ventilation rooms, transformer rooms, separating device rooms of broadcast stations with capacity of 150 kW or more, receiving stations with the number of at least 20, fixed stations of space communications with capacity of more than 1 kW, television relay stations with capacity of 25-50 kW, network nodes, inte-city and inter-provincial telephone exchanges, telegraph stations, terminal amplifying stations and regional communication centers |
- |
Regardless of area |
3.2. |
Maintenance-free and maintained without the evening and night ships: technical workshops of terminal amplifying stations, intermediate relay stations, transmitting and receiving radio stations |
Regardless of area |
Regardless of area |
3.3. |
Maintenance-free base stations of cellular mobile radio systems and maintenance-free relay stations of cellular mobile radio systems |
With area of 24 m2 or more |
Regardless of area |
3.4. |
Digital switchboard rooms, telephone control centers; computation centers of post offices of provinces and cities with total volume of buildings: |
|
|
3.4.1. |
40 000 m3 or more |
With area of 24 m2 or more |
Regardless of area |
3.4.2. |
Less than 40 000 m3 |
- |
Regardless of area |
3.5. |
ATS sites where switching equipment of electronic or quasi-electronic type is installed together with ECM, used as a control complex, input-output devices; premises of electronic switching stations, networks, document electric communication centers with a capacity of: |
|
|
3.5.1. |
10 000 numbers, channels or connection points or more |
Regardless of area |
Regardless of area |
3.5.2. |
Fewer than 10 000 numbers, channels or connection points |
- |
Regardless of area |
3.6. |
Dedicated rooms for dividing and connecting equipment using computers to control automatic telephone exchanges with station capacity: |
|
|
3.6.1. |
10 000 inter-provincial and inter-city channels or more |
With area of 24 m2 or more |
Regardless of area |
3.6.2. |
Fewer than 10 000 inter-provincial and inter-city channels |
- |
Regardless of area |
3.7. |
Rooms for processing, sorting, storage and delivery of dispatches, correspondence and printed media |
With area of 500 m2 or more |
Regardless of area |
4. |
Transport rooms |
|
|
4.1. |
Rooms and compartments for production, repair and fabrication of trains, electric trains, ships (electrical machines, equipment, repair and fabrication of wagons, wheels, engines, etc.) |
With area of 1 000 m2 or more |
With area of 300 m2 or more |
4.2. |
Rooms and component constructions of the subway system (except for aisles and passenger lounges, subway tunnels, water pumping stations, heating equipment, ventilation chambers) |
Regardless of area |
Regardless of area |
4.3. |
Rooms for repair, maintenance and storage of automobiles |
|
|
4.3.1. |
Chambers for repair, maintenance and storage of automobiles |
With area of 700 m2 or more |
With area of 300 m2 or more |
4.3.2. |
Rooms for storage of automobiles in buildings of other purpose (except for homes) situated: |
|
|
4.3.2.1. |
Above ground |
3 automobiles or more |
Regardless of area |
4.3.2.2. |
In basement or semi-basement (even under bridge) |
Regardless of area |
Regardless of area |
4.4. |
Rooms for disassembling and assembling aircraft engines, flying equipment, chassis and wheels for airplanes and helicopters; rooms for production and repair of aircraft engines |
Regardless of area |
Regardless of area |
5. |
Rooms of public purposes |
||
5.1. |
Storage rooms in libraries and archives with the number of documents and books: |
|
|
5.1.1. |
250 000 units or more |
Regardless of area |
Regardless of area |
5.1.2. |
Fewer than 250 000 units |
- |
With area of 300 m2 or more |
5.2. |
Display and exhibition rooms 3) |
With area of 1 000 m2 or more |
With area of 500 m2 or more |
5.3. |
Rooms for storage and display of museum values 3) |
Regardless of area |
Regardless of area |
5.4. |
In cultural and entertaining buildings (theaters, clubs, concert and film and concert halls, event venues, cultural houses, circuses, studios, etc.) having stages and auditoriums: |
|
|
5.4.1. |
With seating capacity of 700 seats or more 4) |
Regardless of area |
Regardless of area |
5.4.2. |
With seating capacity of 400 seats or more and stage area of 100 m2 or more 4) |
Regardless of area |
Regardless of area |
5.4.3. |
Warehouses for ornaments, utensils and props |
With area of 100 m2 or more |
With area of 100 m2 or more |
5.5. |
Studios |
With area of 1 000 m2 or more |
With area of 300 m2 or more |
5.6. |
Rooms for storage of cash in banks and treasuries |
With volume of 100 m3 or more |
Regardless of area |
5.7. |
Rooms for storage of hand baggage, flammable materials in buildings stations (including air terminals) situated: |
||
5.7.1. |
In basement or semibasement |
Regardless of area |
Regardless of area |
5.7.2. |
On the ground |
With area of 300 m2 or more |
With area of 300 m2 or more |
5.8. |
Chambers and rooms for storage of flammable materials located: |
||
5.8.1. |
Under tribunes of any capacity in the indoor sports facilities |
With area of 100 m2 or more |
With area of 100 m2 or more |
5.8.2. |
In buildings of indoor sports facilities with a capacity of 800 spectators or more |
With area of 100 m2 or more |
With area of 100 m2 or more |
5.8.3. |
Under tribunes with capacity of 3 000 spectators or more in outdoor sport facilities |
With area of 100 m2 or more |
With area of 100 m2 or more |
5.9. |
Dedicated server rooms |
With area of 24 m2 or more |
With area of 24 m2 or more |
5.10. |
Trade rooms in buildings of other purposes: |
||
5.10.1. |
In basement or semibasement |
With area of 200 m2 or more |
Regardless of area |
5.10.2. |
Above ground |
With area of 500 m2 or more |
With area of 500 m2 or more |
5.11. |
Rooms for sale of flammable and highly flammable liquids (except for goods contained in cans and bottles with a capacity of not more than 20 liters) |
Regardless of scale |
Regardless of scale |
NOTES: 1) An automatic fire extinguishing system is not required to be installed in the entire room in case it has been equipped with an automatic fire alarm system and all electrical and electronic equipment (including equipment of the automatic process control system) are protected by automatic fire extinguishing installations according to national standards, international and foreign standards permitted for application in Vietnam. 2) In order to protect these rooms, the automatic fire extinguishing system must not cause damage or malfunction to the equipment even if it is accidentally activated. 3) This requirement does not apply to rooms used for temporary exhibitions. When placing cars in the exhibition and trade rooms, these premises must be equipped with an automatic fire extinguishing system in accordance with 5.3 and 5.11 of this table.
4) If the stage is 100 m2 or more, there must be a fire separation (a drencher water curtain or a fire curtain with a fire-resistance rating at least El 60) between the stage area and the audience seating area. The area of the rooms specified in this Table is understood as the area of a part of the building surrounded by fire barriers with fire-resistance rating: walls, floors and partitions - at least El 45. Where the rooms are separated by structures with fire-resistance rating less than El 45, the area of the rooms is the total area of these rooms and the functional part of the room to which the highest equipment requirements apply shall be taken into account in accordance with regulations of this Annex. NOTE: For production rooms and storerooms, including laboratories and workshops with an area of more than 50 m2 in F1, F2, F3 and F4 buildings, they comply with the provisions of this standard applicable to F5 rooms. |
Table A.4. For equipment
No. |
Protected objects |
Automatic fire extinguishing system |
Automatic fire alarm system |
1. |
Paint shops with highly flammable or flammable liquids |
Regardless of type |
Regardless of type |
2. |
Drying chambers |
Regardless of type |
Regardless of type |
3. |
Collectors (hoppers) for collection of combustible waste 1) |
Regardless of type |
Regardless of type |
4. |
Oil power transformers: |
||
4.1. |
With voltage of 500 kV or more |
Regardless of power |
Regardless of power |
4.2. |
With voltage of 220 kV |
200 MVA or more |
Regardless of power |
4.3. |
With voltage of 110 kV, installed in power plants |
63 MVA or more |
63 MVA or more |
4.4. |
With voltage of 110 kV, installed in chambers of electrical substations |
63 MVA or more |
Regardless of power |
5. |
Transformers located in rooms of buildings of other purpose (exclusive of those in section 4 of this table) |
63 MVA or more or 110 KV or more |
Regardless of power |
6. |
Test stations of mobile power stations and units with diesel and petrol-electric generating set assembled on trucks and trailers |
Regardless of area |
- |
7. |
Tanks for highly flammable liquids located above ground |
3 m3 or more |
- |
NOTES: 1) Automatic fire extinguishing system may be replaced with automatic fire extinguishing system. |
NOTES:
"-" in the tables in Annex A indicates that it is not mandatory to be equipped with an automatic fire alarm/automatic fire extinguishing system (except for rooms, areas/items located buildings subject to protection by the automatic fire alarm/automatic fire extinguishing system according to Table A.1).
Annex B
(normative)
Equipment of indoor hose reel systems
Table B.1 - Equipment of indoor hose reel systems
No. |
Type of building or construction |
Scale |
1. |
Homes and public constructions |
|
1.1. |
Single-family homes |
7 storeyed or more |
1.2. |
Apartment buildings, tenements, dorms, hotels, guest houses, motels, inns and accommodation establishments founded according to regulations [1] (except for camping sites); multi-function buildings 1) |
5 storeyed or more or 5 63 MVA or with volume of 5 000 m3 or more |
1.3. |
Premises of regulatory authorities at all levels, office buildings of enterprises, socio - political organizations, post offices, radio and television stations, telecommunications facilities, communication equipment installations, data management and storage centers |
6 storeyed or more or with volume of 5 000 m3 or more |
1.4. |
Theaters, cinemas, circuses, halls |
300 seats or more or with volume of 10 000 m3 or more |
1.5. |
- Amusement parks, zoos, aquariums. - Museums, exhibition buildings, art galleries, archive buildings, fair buildings, cultural buildings, religious buildings. - Stadiums, sports stadiums, indoor sports palaces, fitness and sports centers, race tracks, shooting ranges and other sports facilities established in accordance with applicable laws [6], [8], - Motor vehicle registries, stores for sale, repair and maintenance of automobiles, motorcycles and mopeds. |
6 storeyed or more or with volume of 5 000 m3 or more |
1.6. |
Karaoke, discotheque, bar and night club service buildings |
|
1.6.1. |
Situated in basement or semi-basement |
Regardless of scale |
1.6.2. |
Situated above ground |
|
1.6.2.1. |
One or two storeyed |
With area of 300 m2 or more |
1.6.2 2. |
Three storeyed or more |
Regardless of area |
1.7. |
Event centers, markets, supermarkets, shopping malls |
Regardless of scale |
1.8. |
People with disabilities-care institutions |
Regardless of scale |
1.9. |
Air traffic control towers, airport terminals, railway terminals; gondola lift waiting lounges; seaport, inland port and inland waterway ports service buildings, bus stations, rest stops |
6 storeyed or more or with volume of 5 000 m3 or more |
1.10 |
Schools and educational institutions (except for nurseries); buildings for medical examination and treatment and patient dormitories of hospitals, health stations, clinics, sanitariums, rehabilitation and orthopedic centers, centers for disease control and prevention, health centers, other health facilities according to applicable regulations [3] |
3 storeyed or more or with volume of 2 000 m3 or more |
1.11 |
Nurseries, kindergartens, preschools |
100 children or more or with volume of 3 000 m3 or more or 03 storeyed or more |
1.12 |
Cultural buildings, bookstores, libraries, beauty salons, massage service buildings, electronics stores, department stores, convenience stores and stores for sale of highly flammable goods and substances |
With volume of 5 000 m3 or more |
1.13 |
Restaurants, food and beverage stores |
5 storeyed or more or with volume of 5 000 m3 or more |
2. |
Production buildings, warehouses |
With area of 500 m2 or with volume of 2 500 m3 or more |
3. |
Car and moped garages and showrooms, premises for car and moped maintenance |
|
3.1. |
Of enclosed type |
With volume of 500 m3 or more |
3.2. |
Of exposed type (except for automated parking garages) |
With volume of 3 000 m3 or more |
NOTES: 1) A multi-function building is not subject to protection by an indoor hose reel system but any of its functional part whose scale is subject to protection by an indoor hose reel system according to Table B.1, such functional part must be equipped with the indoor hose reel system. If a multi-function building has a functional part used for provision of karaoke, discotheque, bar or night club service on the third floor or more, it is required to be equipped with an indoor hose reel system. |
Annex C
(normative)
Equipment of outdoor hose reel systems
Table C.1 - Equipment of outdoor hose reel systems
No. |
Type of building or construction |
Scale |
1. |
Urban areas, economic zones, industrial parks, industrial clusters, export-processing zones, hi-tech zones and other dedicated areas in accordance with applicable regulations subject to approval by a district or higher-level authority [5] |
Regardless of scale |
2. |
Nursing homes, people with disabilities-care institutions |
Regardless of scale |
3. |
Premises of regulatory authorities at all levels, office buildings of enterprises, socio - political organizations, cultural buildings, religious buildings |
6 storeyed or more or with volume of 5 000 m3 or more |
4. |
Apartment buildings, tenements, dorms, multi-function buildings |
6 storeyed or more or with volume of 5 000 m3 or more |
5. |
Nurseries, kindergartens, preschools |
100 children or more or with volume of 3 000 m3 or more |
6. |
Schools and other educational institutions (except for nurseries) |
3 storeyed or more or with volume of 5 000 m3 or more |
7. |
Buildings for medical examination and treatment and patient dormitories of hospitals, health stations, clinics, sanitariums, rehabilitation and orthopedic centers, centers for disease control and prevention, health centers, other health facilities according to applicable regulations [3] |
3 storeyed or more or with volume of 3 000 m3 or more |
8. |
Theaters, cinemas, circuses |
Regardless of scale |
9. |
Convention and event centers |
Regardless of scale |
10. |
Beauty salons, massage service buildings |
With volume of 1 500 m3 or more |
11. |
Clubs, amusement parks, zoos, aquariums |
6 storeyed or more or with area of 10 000 m2 or more |
12. |
Karaoke, discotheque, bar and night club service buildings |
3 storeyed or more or with volume of 1 500 m3 or more or situated in basement or semi-basement |
13. |
Markets, shopping malls, supermarkets |
Regardless of scale |
14. |
Electronics stores, department stores, convenience stores and stores for sale of highly flammable goods and substances |
With volume of 5 000 m3 or more |
15. |
Restaurants, food and beverage facilities |
5 storeyed or more or with volume of 5 000 m3 or more |
16. |
Guest houses, motels, inns and accommodation establishments founded according to prevailing regulations [1] |
6 storeyed or more or with volume of 5 000 m3 or more |
17. |
Museums, libraries, art galleries, exhibition buildings, archive buildings, bookstores, fair buildings |
With volume of 5 000 m3 or more |
18. |
Post offices, radio and television stations, telecommunications facilities, communication equipment installations, data management and storage centers |
6 storeyed or more or with volume of 5 000 m3 or more |
19. |
Stadiums |
6 storeyed or more or with volume of 5 000 m3 or more |
20. |
Sports stadiums, indoor sports palaces, fitness and sports centers, race tracks, shooting ranges and other sports facilities established in accordance with applicable laws [6], [8] |
6 storeyed or more or with volume of 5 000 m3 or more |
21. |
Airports; air traffic control towers; seaports; inland ports; inland waterway ports |
Regardless of scale |
22. |
Coach station waiting lounges, gondola lift waiting lounges, rest stops |
6 storeyed or more or with volume of 5 000 m3 or more |
23. |
Component items of subway constructions; motor vehicle registries, stores for sale, repair and maintenance of automobiles, motorcycles and mopeds |
6 storeyed or more or with volume of 5 000 m3 or more |
24. |
Car and moped garages and showrooms, premises for car and moped maintenance |
With volume of 3 000 m3 or more |
25. |
Nuclear facilities; facilities for production, trading, storage of industrial explosives and explosive precursors; warehouse of industrial explosives and explosive precursors; delivery ports for industrial explosives and explosive precursors; warehouses of weapons and support instruments; facilities for extraction, processing, production, transport, trading and storage of petroleum and petroleum products, and gas on land; petroleum and petroleum products terminals, gas terminals; delivery ports for petroleum and petroleum products, and gas; petrol and oil stores; petrol and oil filling stations; |
Regardless of scale |
26. |
Facilities for extraction, processing, production, transport, trading and storage of petroleum and petroleum products, and gas on land; petroleum and petroleum products terminals, gas terminals; delivery ports for petroleum and petroleum products, and gas; petrol and oil filling stations; highly flammable liquid filling stations; gas trading facilities |
Regardless of scale |
27. |
Industrial facilities, production buildings, warehouses and constructions of similar purposes |
|
27.1. |
Fire and explosion hazard classes A, B, C |
With area of 300 m2 or with volume of 1 500 m3 or more or 2 storeyed or more |
27.2. |
Fire and explosion hazard classes D, E |
With area of 500 m2 or with volume of 2 500 m3 or more |
28. |
Electrical substations |
With voltage of 110 kV or more |
29. |
Power plants |
Regardless of scale |
30. |
Basements intended for production, storage and use of flammable and explosive substances |
With volume of 1 000 m3 or more |
31. |
Warehouses of pyrophoric goods and objects or goods and objects whose packages are flammable |
With volume of 3 000 m3 or more |
Annex D
(normative)
Equipment of fire-fighting vehicles
Table D.1 - Equipment of fire-fighting vehicles
No. |
Objects |
Scale |
Fire engines, pieces |
Fire ships, pieces |
Portable fire pumps, pieces |
1 |
Warehouses |
||||
1.1 |
Storerooms |
At national level |
1 |
|
|
1.2 |
Storerooms |
At ministerial and sectoral levels |
|
|
1 |
1.3 |
Petroleum and petroleum products terminals |
With volume of more than 100 000 m3 |
2 |
|
|
1.4 |
Petroleum and petroleum products terminals |
With volume of 50 000 to 100 000 m3 |
1 |
|
|
1.5 |
Petroleum and petroleum products terminals |
With volume of more than 50 000 m3 |
|
|
1 |
2 |
Airports, seaports |
||||
2.1 |
Airports |
International |
3 |
|
|
2.2 |
Airports |
Domestic |
2 |
|
|
2.3 |
Seaports |
Of special class, class I |
2 |
1 |
|
2.4 |
Seaports |
Class II |
1 |
1 |
|
2.5 |
Seaports |
Class III |
|
|
1 |
3 |
Production facilities |
||||
3.1 |
Thermal power plants1) |
200 MW or more |
1 |
|
|
3.2 |
Hydropower plants1) |
300 MW or more |
1 |
|
|
3.3 |
Thermal power plants and hydropower plants |
With capacity less than above capacity |
|
|
1 |
3.4 |
Nuclear power plants |
Regardless of capacity |
2 |
|
|
3.6 |
Paper mills |
With capacity of more than 35 000 tonnes/year |
1 |
|
|
3.7 |
Textile mills |
With capacity of more than 20 million square meters/year |
1 |
|
|
3.8 |
Cement plants |
With capacity of more than 1 million tonnes/year |
1 |
|
|
3.9 |
Nitrogenous fertilizer plants |
With capacity of 180 000 tonnes or more /year |
1 |
|
|
3.10 |
Steel mills |
With capacity of 300 000 tonnes of billets or more/year |
1 |
|
|
3.11 |
Paper mills, textile mills, cement plants, nitrogenous fertilizer plants, steel mills |
With capacity less than above capacity |
|
|
1 |
3.12 |
Oil refineries, petrochemical and oil refineries, petrochemicals |
Regardless of capacity |
2 |
|
|
3.13 |
Gas processing facilities |
With capacity of 15 million m3 of gas or more/24 hours |
1 |
|
|
3.14 |
Mining facilities |
With capacity of 300 000 tonnes or more /year |
1 |
|
|
3.15 |
Gas processing facilities, mining facilities |
With capacity less than above capacity |
|
|
1 |
4 |
Industrial parks, export-processing zones, hi-tech zones, industrial clusters |
||||
4.1 |
Industrial parks, export-processing zones, hi-tech zones |
With area of more than 300 ha |
3 |
|
|
4.2 |
Industrial parks, export-processing zones, hi-tech zones |
With total area exceeding 150 ha but not exceeding 300 ha |
2 |
|
|
4.3 |
Industrial parks, export-processing zones, hi-tech zones, industrial clusters |
With total area exceeding 50 ha but not exceeding 150 ha |
1 |
|
|
4.4 |
Industrial parks, export-processing zones, hi-tech zones, industrial clusters |
With total area of less than 50 ha |
|
|
1 |
NOTES: 1): For thermal power plants with capacity of 200 MW or more and power plants with capacity of 300 MW or more in the same area (or adjacent to each other) and under the same operator, only 01 fire engine is required. |
Annex E
(normative)
Equipment of rudimentary demolition tools
Table E.1 - Equipment of rudimentary demolition tools
No. |
Objects |
Scale |
Quantity |
1. |
Production buildings |
Regardless of scale |
1 set of rudimentary demolition tools includes: + Rescue axe (2 kg in weight, 90 cm handle, high-carbon steel); + Crowbar (one sharp end, one flattened end; 100 cm in length); + Sledgehammer (high-carbon steel, 5 kg in weight, 50 cm handle); + Bolt cutter (60 cm in length, cutting load of 60 kg); |
2. |
Warehouses |
||
3. |
Tenements, hotels, apartment buildings, food and beverage facilities |
||
4. |
Administrative authorities, schools, hospitals |
||
5. |
Railway stations, other public constructions |
||
6. |
Theaters, cinemas, halls, karaoke, discotheque, bar and night club service buildings |
||
7. |
Permanent and semi-permanent markets, shopping malls |
Annex F
(normative)
Equipment of filter masks and self-contained breathing apparatus
Table F.1 - Equipment of filter masks and self-contained breathing apparatus
No. |
Objects |
Scale |
Quantity, pieces |
1. |
Hotels, guest houses, motels; inns and accommodation establishments founded according to regulations [1] (except for camping sites) 3 storeyed or more |
Regardless of scale |
Equip filter masks on all storeys with a required quantity of 1 piece/person (including guests and regular staff) |
2. |
Facilities providing karaoke, discotheque, bar or night club services |
Regardless of scale |
Equip filter masks on all storeys. The quantity of masks on a storey depends on the number of persons present at the same time in a room with the largest area of that floor with a required quantity of 01 person/piece. |
3. |
Nuclear facilities. |
Regardless of scale |
Equip at least 03 self-contained breathing apparatus |
4. |
Airports, seaports. |
Regardless of scale |
|
5. |
Petroleum and gas extraction and processing facilities |
Regardless of scale |
|
6. |
Coal mining facilities |
Regardless of scale |
|
7. |
Weapon and explosive material production facilities and warehouses |
Regardless of scale |
|
8. |
National stockpile; petroleum and petroleum products terminals |
With volume of more than 15 000 m3 |
|
9. |
Hydropower plants |
300 MW or more |
|
10. |
Thermal power plants |
200 MW or more |
|
11. |
Paper production facilities |
With capacity of 35 000 tonnes or more /year |
|
12. |
Textile facilities |
With capacity of 25 million m2 or more /year |
|
13. |
Nitrogenous fertilizer production facilities |
With capacity of 180 000 tonnes or more /year |
|
14. |
Industrial parks, export-processing zones, hi-tech zones, industrial clusters |
With area of 50 ha or more |
|
15. |
High-rise buildings |
With height of 75 m or more high or with 2 basements or more |
|
16. |
Theaters, cinemas |
Regardless of scale |
Annex G
(normative)
Equipment of public address and evacuation instruction systems
Table G.1 - Equipment of public address and evacuation instruction systems
No. |
Objects |
Scale |
1. |
Homes and public constructions |
10 storeyed or more or with 2 basements or more |
2. |
Crowded public constructions: Theaters, cinemas, halls, karaoke, discotheque, bar and night club service buildings, hospitals, nursing homes and constructions of similar purposes |
50 persons or more on 1 floor |
3. |
Automobile and moped garages of enclosed type (including independent garages and garages in buildings of other purposes) |
With area of 18 000 m2 or more |
4. |
Production buildings and warehouses |
With area of 18 000 m2 or more and 50 persons or more on 1 floor |
Annex H
(normative)
Equipment of initial fire fighting facilities
Table H.1 - Equipment of initial fire fighting facilities
No. |
Name of construction item |
Sand drum, m3 |
Shovel, piece |
Blanket 1x2(m), piece |
1. |
Warehouses and stores containing liquid goods with an ignition temperature > 45°C |
1 m3 for every 350 m2 of floor |
2 pieces for every 350 m2 of floor |
1 piece for every 350 m2 of floor |
2. |
Production and processing workshops using mechanical equipment, drying ovens, welding machines |
|
|
1 piece for every 200 m2 of floor |
Bibliography
[1]. Law on Tourism.
[2]. Law on Education.
[3]. Law on Medical Examination and Treatment
[4]. Law on Fire Prevention and Fighting
[5]. Law on Planning.
[6]. Law on Physical Training and Sports.
[7]. Law on Amendments to some Articles of the Law on Fire Prevention and Fighting.
[8]. Law on Amendments to some Articles of the Law on Physical Training and Sports.
[9]. Government’s Decree No. 136/2020/ND-CP dated November 24, 2020 providing guidelines for a number of Articles of Law on Fire Prevention and Fighting and Law on Amendments to Law on Fire Prevention and Fighting.
[9]. Government’s Decree No. 149/2020/TT-BCA dated December 21, 2020 providing guidelines for Law on Fire Prevention and Fighting, Law on Amendments to Law on Fire Prevention and Fighting and the Government’s Decree No. 136/2020/ND-CP dated November 24, 2020 providing guidelines for a number of Articles of Law on Fire Prevention and Fighting and Law on Amendments to Law on Fire Prevention and Fighting.
[11]. Circular No. 17/2022/TT-BCA dated February 05, 2022 on management, preservation, maintenance of fire prevention, firefighting and rescue equipment.
[12]. Circular No. 147/2020/TT-BCA dated December 21, 2020 on fire safety and rescue measures for karaoke and nightclub establishments.
[13]. Circular No. 150/TT-BCA dated December 31, 2020 on provision of fire prevention and fighting and rescue equipment to neighborhood watches, internal firefighting forces and specialized firefighting forces.
[14]. Document No.20/VBHN dated May 09, 2014 consolidating Joint Circular joinly promulgated by Ministry of Trade and Ministry of Public Security No. 15/2001/TTLT-BTM-BCA dated May 10, 2021 on provision and management of fire-fighting facilities in petroleum and petroleum products terminals.
[16]. QCVN 01:2020/BCT National technical regulation on design requirements for petrol filling stations;
[17]. QCVN 06:2022/BXD National Technical Regulation on Fire safety of Buildings and Constructions.
[18]. QCVN 01:2019/BCT National technical regulation on safety in the process of producing, testing, performing check and acceptance, storage, transportation, use, disposal of industrial explosive materials and storage of explosive precursors.
[19]. QCVN 10:2012/BLDTBXH National technical regulation on occupational safety with gas filters used in masks and respirators.
[20]. QCVN 13:2018/BXD National technical regulation on Car Parking.
[21]. TCXDVN 33:2006 Water Supply - Distribution System and Facilities. Design Standard.
[22]. TCN 48:1996 Fire protection for trade and services enterprises - General provisions.
[23]. TCN 58:1997 Fire protection for markets and shopping malls – Safety requirements for operation.
[24]. TCVN 9310-3:2012 Fire protection - Vocabulary - Part 3: Fire detection and alarm.
[25]. TCVN 9310-4:2012 Fire protection - Vocabulary - Part 4: Fire extinguishing equipment.
[26]. TCVN 3254:1989. Fire safety - General requirements
[27]. TCVN 3991:2012 Standard for fire protection in building design - Terminology - Definitions.
[28]. TCVN 4245:1996 Amendment 1. Safety engineering requirements in production and utilization of oxygen, acetylene
[29]. TCVN 4317:1986 Warehouses - Basic principles for design.
[30]. TCVN 4879:1989 Group T - Fire protection - Safety signs.
[31]. TCVN 5040:1990 Group T - Fire prevention and protection equipments - Graphical symbols used for protection schemes.
[32]. TCXDVN 5065:1996 Hotels - Design standard.
[33]. TCVN 5279:1990. Fire and explosion safely - Combustible dusts - General requirements.
[34]. TCVN 13249:2020 (ISO 13943:2017) Fire safety - Vocabulary.
[35]. TCVN 12823-4:2020 Mobile Offshore Units - Part 4: Safety Equipment and Fire Protection.
[36]. TCVN 6160:1996 Fire protection - High-rise buildings - Design requirements.
[37]. TCN 6161:1996 Fire protection - Markets and shopping centers - Design requirements.
[38]. TCVN 6174:1997 Amendment 2. Industrial explosion materials - Safety code for production, explosion test, check and acceptance.
[39]. TCVN 6304:1997 Liquefied petroleum gas cylinders - Safety requirements in storage, handling and transportation.
[40]. TCVN 6379:1998. Fire protection equipment - Fire hydrant - Technical requirements.
[41]. Codes of Practice for minimum fire service installations and equipment and inspection and testing of installations and equipment. March, 1994.
[42]. СП 486.1311500.2020 Перечень зданий, сооружений, помещений и оборудования, подлежащих защите автоматическими установками пожаротушения и системами пожарной сигнализации. (Fire protection systems. Fire alarm systems and automation of fire protection systems. Norms and rules of design. The list of buildings, structures, premises and equipment, subject to protection by automatic extinguishing and fire alarm systems. Russian Emergency Situations Ministry).
[43]. СП 8.13130.2020 Требования пожарной безопасности. Наружное противопожарное водоснабжение. (The fire protection systems. Outdoor fire-fighting water supply. Fire safety requirements. Russian Emergency Situations Ministry).
[44]. СП 10.13130.2020 Системы противопожарной защиты. Внутренний противопожарный водопровод. (Fire protection system. Installation of standpipe and hose systems. Designing and regulations rules. Russian Emergency Situations Ministry).
[45]. KOFEIS 0106 (Korea).
Index
Foreword
1 Scope
2 Normative references
3 Terms and definitions
4 General provisions
5 Regulations on Equipment and installation of fire protection equipment and systems
Annex A (normative) Equipment of automatic fire alarm systems, local fire alarms devices and automatic fire extinguishing system
Annex B (normative) Equipment of indoor hose reel systems
Annex C (normative) Equipment of outdoor hose reel systems
Annex D (normative) Equipment of fire-fighting vehicles
Annex E (normative) Equipment of rudimentary demolition tools
Annex F (normative) Equipment of filter masks and self-contained breathing apparatus
Annex G (normative) Equipment of public address and evacuation instruction systems
Annex H (normative) Equipment of initial fire fighting facilities
Bibilography